| Input |
| Nominal Voltage |
230V |
| Input Frequency |
47Hz ~ 65Hz, 50/60Hz auto-sensing |
| Efficiency (Normal mode) |
97% |
| Noise Filtering |
Full time EMI/RFI filtering |
| Overcurrent protection |
Re-settable overcurrent protector |
| Voltage Range |
140V ~ 310V |
| AVR Range (2 Bucks, 2 Boosts) |
Enhanced Buck: +28% of selected nominal voltage
Buck mode: +10% of selected nominal voltage
Boost mode: -10% of selected nominal voltage
Enhanced Boost: -25% of selected nominal voltage |
| Surge Protection |
440 Joules |
| Output |
| Power Level at nominal input |
3000W |
| Output Voltage |
230V |
| Voltage Waveform |
Pure Sine wave |
| Crest Factor |
3:1 |
| Output Frequency (Synchronized to Mains) |
Auto Select for 50/60Hz
47Hz ~ 55Hz for 50Hz nominal
56Hz ~ 65Hz for 60Hz nominal |
| Regulation (Nominal) |
±10% nominal voltage |
| Regulation (Battery mode) |
±3% of selected output voltage (adjustable with the remote set-up software) |
| Transfer time |
Blackout: 3ms typical
Over- and under-voltages: 1ms typical
Battery mode to Normal mode: 1ms typical |
| Overcurrent protection |
Overload alarm level 100% ~ 120%
Overload shutdown level 120% ~ 190%
(Adjustable by using the remote set-up software) |
| Battery |
| Battery type |
Lead-Acid 50Ah ~ 500Ah (Recommended) |
| Voltage |
48Vdc |
| Charging method |
Smart pulse charging with two charging modes: Quick charging when battery is not fully charged, trickle
charging when battery is 90% fully charged. |
| Maximum charging current |
30A |
| Average charging voltage for each battery |
Quick charging mode: 14V maximum.
Trickle charging mode: 13.5V (adjustable with the remote set-up software) |
| Protection |
Overcurrent protection & charging overvoltage protection (SCR control)
Thermal protection (CPU control)
When the temperature inside the unit is over 45°C, the charger stops charging for 2 minutes followed by 2
minutes charging. The cycle will repeat until the temperature is lower than 44°C. |
| Monitoring |
Smart monitoring & warning for failed battery or open-circuit battery.
Battery auto-detection each time at power ON or every 6 days. |
| Solar Charger (optional) |
| Rating voltage |
48V |
| DC input range |
48 ~ 84Vdc |
| Charging method |
Constant voltage with current limited by PWM control |
| Charging voltage |
54Vdc |
| Power rating |
1000W (54Vdc @ 18.5A) |
| Protection |
DC input polarity protection, DC input short circuit protection (when battery is connected), DC output
overcurrent protection |
| Communication & Management |
| Standard Interface port |
UPSilon2000 compatible; optional for RS232 and/or USB. |
| Optional Interface port |
RJ45 (Surge protection), DB9, SNMP (external type) |
| Control panel |
LCD |
| Audible alarm |
Alarm on battery: Low battery & Battery over voltage
Alarm on abnormal operation: Overload, Short-circuit, & Overheat |
| Green mode function (Auto-shut-off in blackout) |
1% to 14% of full load (adjustable by using the remote set-up software)
The default setting is OFF. |
| Cooling fan control |
Auto on/off, controlled by temperature & operation mode |
| Environmental |
| Operating Temperature |
Up to 1500 meters: 0°C to 40°C (32°F to 104°F) |
| Transit/Storage Temperature |
-15°C to 55°C (5°F to 131°F) |
| Relative Humidity |
5 - 95% non condensing |
| Operating Altitude |
0 ~ 3000 meters |
| Physical |
Dimensions
Unit / Shipping (D×H×W) |
22×44×27cm / 36×61×41cm |
| Weight (Net / Gross) |
38kg / 41kg |
| Packing |
Export carton for each unit, 16 - 30 units per pallet |